T2-A2-6A1E | 50 Amp Terrapin Station II™, Feed Thru Spider Box to GFCI Duplex/L6-30 Receptacles | LEX Products

50 Amp Terrapin Station II™, Feed Thru Spider Box to GFCI Duplex/L6-30 Receptacles

T2-A2-6A1E T2-A2-6A1E

50 Amp Terrapin Station II™, Feed Thru Spider Box to GFCI Duplex/L6-30 Receptacles

50A 125/250 VAC, (1) California Style CS63 Male (Inlet) to (6) NEMA 5-20 (Edison) GFCI Straight Blade Receptacles (Outlets) and (1) NEMA L6-30 Locking Receptacle (Outlet), Feed Thru, Terrapin II™

Part NumberT2-A2-6A1E
Markets Entertainment  Industrial 
Rating Outdoor 
EnclosureBox
Input California Style 
Output NEMA 
Amperage50A
Certifications Certification Icon
Data Sheet Print / Save As

Features & Benefits

-Meets UL, NEC and OSHA requirements for events and generator rental
-Meets OSHA Regulation 20 Part 1926, Subpart K standards for open-neutral GFCI protection for enhanced safety
-Heavy duty molded rubber enclosure is fully insulated and resistant to shock, impact and corrosion for years of trouble-free service versus painted metal
-Thermal magnetic circuit breakers are located under a heavy duty rubber, waterproof, self-closing lid for enhanced breaker protection
-Weather resistant GFCI protection helps to prevent unsafe operating conditions and nuisance tripping
-GFCI module possesses LED beacon to indicate device status
-Locking receptacles provide secure connections that prevent accidental separation
-cULus Listed and TYPE 3R Rainproof for outdoor use
-Feed thru spider box features allows multiple boxes to be placed along one feed
-Spring-loaded covers protect receptacles and inlets from dirt and moisture intrusion
-Lightweight and compact for easy portability and storage
-Heavy-duty aluminum legs position these electrical distribution boxes at the NEC regulatory height of 6 inches while allowing for storage and transport stacking
-Molded handle enhances portability while improving stack ability of multiple units

Markets Served

Electrical Distribution, Maintenance, Shipbuilding, Generator Rental, Construction, Outdoor Events, Shelters

Technical Information

Rating: 50 Amp, Double-phase (H,H,N,G), 3-pole, 4-wire, 125/250Y VAC, 60 Hz
Environmental Rating: NEMA Type 3R (Weather Resistant)
Input: (1) California Style CS63, 50 Amp, 3-pole, 4-wire, 125/250 VAC, locking inlet, cover doors, panel mount
Feed Thru: Yes
Main Breaker: None
Output: (6) NEMA 5-20, 20 Amp, 2-pole, 3-wire, 125 VAC, straight blade duplex receptacles, cover doors, panel mount, GFCI open-neutral protected; (1) NEMA L6-30, 30 Amp, 2-pole, 3-wire, 250 VAC, locking receptacle, cover door, panel mount
Overcurrent Protection: (6) 20 Amp, 125 VAC, single-pole, hydraulic magnetic, branch-rated circuit breakers; (1) 30 Amp, 120/240 VAC, double-pole, hydraulic magnetic, branch-rated circuit breaker
Enclosure Type: Terrapin II™
Dimensions: 14.25"L x 14.25"W x 17.50"H
Weight: 29.0lbs
Agency Approval: cULus Listed