The product images shown may represent the range of product, or be for illustration purposes only and may not be an exact representation of the product.
200A 480/277 VAC, (5) 16 Series Cams, Power Input Panel / Rotary Style Manual Transfer Switch, Service Entrance Rated
Part Number | PXM02US43-KE-K-AE |
---|---|
Category | Manual Transfer Switch |
Markets | Industrial |
Environmental Rating | Outdoor |
Amperage | 200A |
Certifications | |
Data Sheet | Print / Save As |
- This Service Entrance Rated (US Only) rotary style manual transfer switch is critical in switching power from utility to temporary power for the complete electrical system
- Safe, convenient and economical way to connect and transfer between permanent and temporary power during natural disaster, power grid failure and system maintenance
- The manual, three position switch prevents two sources of power from feeding the system at the same time
- Cables with 16 Series Cam-type devices connect directly to the inputs, saving crucial time in emergency situations while complying to NEC code
- Phase Rotation Monitor (units up to 480V): Quickly monitor the total loss of one or more phases and synchronization of phases
- Convenience Outlets: (2) 20A 120V Weather Resistant Duplex Receptacles protected by (2) GFCI breakers aids in preventing nuisance tripping due to condensation
- Supply power to block heaters and battery chargers with convenience outlets
- Weatherproof construction for installation on building exterior ensures long life
- Units feature an electronic trip circuit breaker that is 100% rated, enabling continuous operation at maximum capacity
- Electronic circuit breaker may be configured in the field to trip between 40% and 100% of its rated capacity
- Cables drop downward for lowest profile against wall
- Tamper proof design limits access to connected cables
- Dead-front panel covers all exposed electrical parts for added safety
- cULus Listed to UL 1008
- Built to satisfy NFPA, National Electrical Code (NEC) standards
Markets Served
Generator Rental, Construction, Industrial, Disaster Relief, Gas Stations, Convenience Stores, Housing Complexes, Schools and other Municipal Facilities
Rating: | 200 Amp, 3 Phase (H,H,H,N,G), 4-Pole, 5-Wire, 480/277 VAC, 35 KA SCCR |
---|---|
Environmental Rating: | NEMA Type 3R (Outdoor Use) |
Input: |
PERMANENT (5) compression single wire lugs (H,H,H), wire range: 350 MCM – 6 AWG, (N,G dual port terminal blocks), wire range: 600 MCM - 2 AWG
|
Output: | (1) set of (5) dual port compression lugs (H,H,H,N,G), wire range: 600 MCM – 2 AWG; (2) NEMA 5-20 (Edison), 20 Amp, 2-pole, 3-wire, 125 VAC, straight blade duplex receptacles, panel mount |
Disconnect Method: | Double Throw Switch |
Overcurrent Protection: |
PERMANENT – (1) 200 Amp, 600 VAC triple-pole, adjustable electronic, branch-rated circuit breaker, 65 KAIC, 100% rated ACCESSORY – (2) 20 Amp, 125 VAC, single-pole, GFCI, hydraulic magnetic, branch-rated circuit breakers |
Enclosure: | Powder Coated Aluminum 5052, 0.1” thick, ANSI 61 gray, wall mounted |
Overall Dimensions: | 42.00"L x 38.00"W x 18.34"D |
Weight: | 276 lbs. |